Abstract
The scenarios of a half wavelength transmission line (HWTL) connected to the original DC asynchronous interconnection system are established based on the quasi-steady state model of HWTL, which include single or double loops of single channel and multi-channel scenarios with different starting and landing points. Firstly, the steady state power flow characters of multi-scenario transmission schemes are studied. The voltage distribution characters of HWTL are analyzed when its transmission power and power factor vary, and the influence of the DC power variation on voltage of HWTL is discussed. Then the transient characters of HWDHTS are explored. The DC commutation failure caused by the fault of HWTL is simulated and the power transfer capacity of HWTL while DC blocking is calculated in this paper.
| Original language | English |
|---|---|
| Pages (from-to) | 366-375 |
| Number of pages | 10 |
| Journal | Global Energy Interconnection |
| Volume | 1 |
| Issue number | 3 |
| DOIs | |
| State | Published - Aug 2018 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Steady state characters
- Transient stability
- UHV DC system
- UHV half-wavelength AC power transmission line
Fingerprint
Dive into the research topics of 'Simulation and analysis of UHV half wavelength and DC hybrid transmission system'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver